HEAT-RESISTANT-HEPR-POWER-UNSCREENED-CABLES-FG7R-FG7OR

TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Max. Short Circuit Temperature: (max. 5 sec.) 250°C
  • Rated Voltage: 0.6/1kV
  • Min. Bending Radius: 8x Cable Outer Diameter
  • Production Standard: CEI 20-13, CEI 20-22 II
    IEC 60502-1, IEC 60332-1-2

CONSTRUCTION

  • Conductor: Electrolytic, Stranded, Copper Wire Class 5
    (IEC 60228, DIN VDE 0295, BS 6360, HD 383)
  • Insulation: Rubber based HEPR G7 Compound
  • Inner Sheath: Seperating foil or PVC Compound
  • Outer Sheath: Flame Retardant PVC Compound

CODE of CABLE

  • FG7R, FG7OR

APPLICATION

These cables can be used for outdoor and indoor power, control
and signaling applications, even in wet environment, in
industries, in public or residential buildings. Suitable for fixed
installations in open air, in tube, canals, masonry, metal
structures, everhead cable trays and for direct or indirect
underground laying.

SECTION RANGE

  • From 1.5mm2 up to 400mm2

CONDUCTOR QUANTITY

  • From 1 core up to 5 cores

COLOUR CODE of CABLE

  • Insulation Colours code could be according to the
    International Standards or customer’s request/demand.
    * Other colours can be produced upon the customer
    requests.

FIRE PERFORMANCE of CABLE SHEATHS

Cables can be supplied with special flame-retardant PVC
outer sheath to comply with the flame test requirements of
IEC 60332 Category A-B and C.