RFCU

TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Max. Short Circuit Temperature: (max. 5 sec.) 200°C
  • Rated Voltage: 0,6/1kV
  • Min. Bending Radius: 8x Cable Outer Diameter
  • Production Standard: NEK TS 606, IEC 60092/353, IEC 60092/350-360, IEC 60332/1-2,
    IEC 60332/3-22 Cat A, IEC 60754 / 1-2,
    IEC 61034 / 1-2 (DIN EN 50268 / 1-2), IEC60811 /403

CONSTRUCTION

  • Conductor: Electrolytic, stranded, annealed copper wire IEC 60228 Class 2 (Class 5 and / or tinned on request)
  • Insulation: Hard grade Ethylene Propylene Rubber (HEPR)
  • Inner Covering: Flame retardant and halogen-free compound
  • Armour: Galvanised steel wire braid
  • Outer Sheath: Flame retardant, halogen-free thermoset compound, SHF2
  • Color: Black and other colors

CODE of CABLE

  • RFCU

APPLICATION

These cables are used for fixed installation for power, control and lighting in both explosion and safe areas, emergency and critical systems.

SECTION RANGE

  • From 1.5mm2 up to 300mm2

CONDUCTOR QUANTITY

  • From 1 core up to 37 cores

COLOUR CODE of CABLE

  • Insulation Colours code could be according to the
    International Standards or customer’s request/demand.
    * Other colours can be produced upon the customer
    requests.

Inquiry Form