MGT+XLPE-LSZH-SWA-OSCR-MP

TECHNICAL DATA

  • Max. Operating Temperature: 90°C
  • Rated Voltage: 300/500V
  • Min. Bending Radius: 10x Cable Outer Diameter
  • Production Standard: EN 50288-7

CONSTRUCTION

Conductor: Electrolytic, stranded, annealed plain copper Wires to IEC 60228 Class 2 (Class 1 or Class 5 and/or tinned on request)

Insulation: Mica tape + XLPE compound to EN50290-2-29

Binder Tape: Polyester foil on overall cable core formed by stranded pairs

Collective Screen: Aluminium/polyester foil with a tinned copper drain wire in direct contact with the metallic side of the foil

Inner Sheath: LSZH compound to EN50290-2-27

Armour: Round galvanized steel wires to EN 10257-1

Outer Sheath: Halogen free flame retardant LSZH compound to EN50290-2-27.

Blue for intrinsically safe cable, Black for UV resistant and/or non-intrinsically safe cable, Gray for indoor applications, Orange or Red for fire resistant

CODE of CABLE

  • CU/MGT+XLPE/OSCR/LSZH/SWA/LZSH; RE-2X(St)HSWAH..CI (MULTIPAIR)

INTRODUCTION

These cables are used to link instruments and control systems for analog or digital signal transmission in both indoor and outdoor applications, petroleum refineries, petrochemistry industry, power plants, natural gas pump stations, indoors and outdoors, dry, damp and wet environments, gas stations, water conveyance systems. Because these cables are not meant to be used for power supply, they should not be connected directly to the mains electrical supply or other low impedance
sources. When circuit integrity is essential in the event of a fire, this product is recommended.

SECTION RANGE

  • From 0.50mm2 up to 2.5mm2

CONDUCTOR QUANTITY

  • From 2 pairs up to 50 pairs

COLOUR CODE of CABLE

  • Insulation Colours code could be according to the
    International Standards or customer’s request/demand.
    * Other colours can be produced upon the customer
    requests.